← Home

The Ultimate HVAC Diagnostic Chart

A measurable, step-by-step HVAC diagnostic chart for licensed MEP technicians and DIY'ers. Every check below is a verifiable reading — voltage, amperage, pressure, temperature, or a coded fault — not speculation. Use it alongside Materva's voice assistant to call out readings hands-free while you work.

How to use this chart

  1. Confirm power and thermostat call before touching the unit.
  2. Read any fault code from the control board LED, ECM, or thermostat display.
  3. Verify the suspected fault with a measurement from the table below.
  4. Replace or repair only after the reading confirms the diagnosis.

1. First-pass safety and power checks

CheckExpected ReadingFault Indication
Line voltage at disconnect (residential split)220–240 VAC<200 VAC: utility/feeder issue
Line voltage (light commercial 3-phase)208 / 230 / 460 VAC ±10%Phase imbalance >2% damages compressor
Control transformer secondary24–28 VAC0 VAC: blown fuse or shorted thermostat wire
Capacitor microfarad (run cap)Within ±6% of rated µF<90% rating: replace
Contactor coil voltage24 VAC across coil when calling0 VAC: check thermostat / safety chain

2. Common HVAC fault codes

Codes vary by manufacturer. Always cross-reference the unit's service label. The table below lists patterns seen across Carrier, Trane, Lennox, Goodman, Rheem, York, and Daikin equipment.

Code / FlashMeaningVerify with
1 flash / "Status OK"Normal operationNo action
2 flashesExternal lockout (low/high pressure switch open)Ohm pressure switches; check refrigerant charge
3 flashesDraft / pressure switch fault (gas furnace)Inducer amp draw + 1.5–2.5" WC negative pressure
4 flashesHigh-limit switch openTemp rise across heat exchanger vs nameplate
5 flashesFlame sensed with no callFlame rod microamps: 1.5–6 µA healthy
7 flashesGas valve circuit fault24 VAC at MV terminals during ignition
E1 / E2 (mini-split)Indoor/outdoor communication lossDC bus voltage on signal wire (typ. 0–56 VDC pulse)
P4 / F3 (VRF/inverter)Compressor IPM or discharge temp faultDischarge line ≤220°F; IPM module resistance
LC / "Lockout"Ignition or safety lockoutCycle power; reread code on next call

3. Refrigerant pressure and superheat/subcool ranges

Pressures depend on refrigerant, indoor/outdoor temperature, and metering device. Use these as starting envelopes for a 95°F outdoor / 80°F indoor / 50% RH day.

RefrigerantSuction (low)Liquid (high)Target Superheat (fixed orifice)Target Subcool (TXV)
R-410A118–135 psig325–400 psig8–15°F8–12°F
R-32120–140 psig340–410 psig8–15°F8–12°F
R-454B115–135 psig320–395 psig8–15°F8–12°F
R-22 (legacy)65–75 psig225–275 psig8–15°F8–12°F

Rule of thumb: low superheat + low subcool = overcharge or restricted airflow. High superheat + low subcool = undercharge or restricted liquid line.

4. Airflow and temperature split

5. Decision flow (text flowchart)

No cooling call response
 ├─ 24 VAC at R-Y at contactor?
 │   ├─ No  → thermostat / float switch / control board
 │   └─ Yes → contactor pulled in?
 │       ├─ No  → coil open / 24V drop under load
 │       └─ Yes → compressor + condenser fan running?
 │           ├─ Fan only       → check run cap, compressor windings
 │           ├─ Compressor only→ check fan cap, motor windings
 │           └─ Both running   → check pressures + superheat/subcool

6. Residential vs commercial vs industrial differences

7. When to stop and escalate

Refrigerant work requires EPA 608 certification. High-voltage 3-phase work and brazing belong to licensed technicians. DIY'ers should stop at the thermostat, filter, condensate, breaker, and capacitor visual inspection — anything past that calls for a pro.

HVAC diagnostic chart FAQ

Short, voice-friendly answers. Materva reads these aloud on request during a session.

What is an HVAC diagnostic chart?
A reference that maps symptoms and fault codes to the exact measurement — voltage, amperage, pressure, or temperature — that confirms the cause before any part is replaced.
What does 2 flashes mean on an HVAC control board?
External lockout. A high or low pressure switch opened. Ohm both switches and check refrigerant charge.
What does 3 flashes mean on a gas furnace?
Pressure switch or draft fault. Measure inducer amp draw and confirm 1.5 to 2.5 inches water column negative pressure at the switch port.
What is normal suction pressure for R-410A?
About 118 to 135 psig on a 95 degree day with an 80 degree return. Pair it with 8 to 12 degrees subcool on a TXV system.
What is a normal temperature split on an AC?
16 to 22 degrees Fahrenheit between return and supply. Below 14 points to overcharge, low airflow, or a weak compressor.
What voltage should I see at the contactor coil?
24 volts AC across the coil when the thermostat is calling. Zero volts means the call is not reaching the unit.
How do I know if my run capacitor is bad?
Measure microfarads with the capacitor isolated. Replace if it reads more than 6 percent below the rated value.
What does E1 mean on a mini-split?
Indoor and outdoor units lost communication. Check the signal wire for the pulsing DC bus voltage and verify tight terminals on both ends.
Can a DIY'er use an HVAC diagnostic chart?
Yes for thermostat, filter, breaker, condensate, and visible capacitor checks. Refrigerant work and 3-phase wiring require a licensed tech.
Can Materva read HVAC codes out loud?
Yes. Speak the code or symptom and Materva walks the verification step by step, hands-free.

Use this chart hands-free

Materva Troubleshoot Pro reads codes back to you, accepts spoken meter readings, and walks the flow above without you putting down your tools. Start a free session or review pricing.

Professional MEP diagnostic aid. Not a substitute for licensed inspection. © 2026 Materva Inc.